Home / What insurers look for / The bottom 6 inches of the walls and flashing
Do I need flashing or noncombustible material on the bottom 6 inches of my walls?
Updated November 7, 2026
Insurers ask for noncombustible material on the bottom 6 inches of every exterior wall. IBHS Essential requires it. It does not have to be flashing. The WUI Code requires it for new work. It is not required by law for an existing home, and it is not in the Board of Forestry's Zone 0 rule.
The Board of Forestry's Zone 0 rule is not in force yet. Insurers and IBHS already use their own requirements.

- Bottom of the wall At least 6 inches of noncombustible material, from the ground up.
- Where a deck meets the wall The same band, just above the deck.
- Deck posts Wood posts get the same covering at the bottom.
What to check
Walk every outside wall. Look at the lowest 6 inches above the ground.
Look again above any deck or patio that touches the wall.
Note wood siding, trim or corners in that band.
Check deck posts and stair bases too.
Ask your insurer what it accepts before you spend money.
What each list says
The lists do not always agree. Here is what each one says about this.
- IBHS Essential
At least 6 inches of noncombustible material applied vertically at the base of all exterior walls. It is measured from the ground up to the nearest horizontal surface, such as a deck or patio. Combustible deck posts need the same covering (sections 2.1.4 and 2.1.5).
- Safer from Wildfires
Noncombustible material 6 inches at the bottom of walls.
- FAIR Plan
6 inches at the bottom of all exterior walls made of noncombustible material.
- San Diego
A voluntary step: a minimum 6-inch metal flashing, applied vertically on the exterior of the wall where a deck meets it.
- WUI Code
For new work in fire hazard zones, the WUI Code requires at least 6 inches of metal flashing or noncombustible material at the ground, deck and roof lines (section 504.5.1). It has been in the 2025 code since January 1, 2026. It does not apply to an existing wall.
- Board of Forestry rule (proposed)
The Board of Forestry rule, as we read it, sets no standard for this.
- For the base of posts, supporting walls and stairs under a deck, IBHS names fiber cement, metal flashing, masonry veneer and stucco.
Sources
- IBHS Wildfire Prepared Home Technical Standard (2025 edition)
- Safer from Wildfires regulation: frequently asked questions, California Department of Insurance, September 2026
- Discounts for dwelling fire and commercial policies, California FAIR Plan, November 15, 2025
- Zone 0 guidelines for existing structures, City of San Diego, April 2026
- 2025 California Wildland-Urban Interface Code, Chapter 5 (section 504.5.1, flashing), via GoCodebook
Related questions
- What do insurers want on and under my deck?
- Do I have to replace my siding?
- Do I need to seal gaps bigger than 1/8 inch?
Want the whole picture? Take the free wildfire course.
Corrections
- November 7, 2026. An earlier version said the 6-inch base rule was proposed for the WUI Code. It has been in the 2025 code since January 1, 2026, for new work.